Permit Number: T02BU00961
Parcel: Unknown

Review Status: Completed

Review Details: GRADING

Permit Number - T02BU00961
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2002 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Drainage and Engineering comments:

1- Verify that the proposed riprap size for the detention basin inlets (d50 = 8", t = 8") can replace the approved size and thickness.
2- The drainage channel in Common Area B-1 appears to have a different cross section from what was approved in the drainage report and tentative plat. Although it appears that the new cross section has more capacity, rate the new section and submit it for approval.
3- Show a detail for the splash pad, west of lot 271.
4- Verify that security barriers are provided where detention basins side slopes exceed 4:1 and depths are 2' or more. Show and specify what kind of barriers on the Grading Plan.
5- Show the pipes on detail D/9. Additionally, show the width dimenstion of the proposed Gabion.
6- Show a cross section for the collector section of Atterbury Wash, showing the proposed Gabion as approved on the tentative plat.
7- The riprap size, thickness and extent for the channel along the south boundary line, should be shown as approved on the tentative plat.
8- Show a detail which includes Gabion for the Attebury flow split area near lot 243 (as was shown on the approved tentative plat).
9- It appears that lots 196-198 do not comply with the requirements of the differential grading provisions.
05/03/2002 MICHAEL ST. PAUL ZONING REVIEW Denied See Engineering.
05/03/2002 LAITH ALSHAMI FLOODPLAIN REVIEW Denied
05/08/2002 LOREN MAKUS NPDES REVIEW Approved
05/10/2002 PATRICIA GILBERT NPPO REVIEW Denied Please submit an approved tentative plat with the approved copy of the native plant preservation plan.

Please add a note to the grading plan, "All grading is required to conform with the approved Native Plant Preservation Plan."

Any necessary preservation fencing needs to be in place and inspected prior to approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/14/2002 MONICA VALDEZ OUT TO CUSTOMER Completed