Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T02BU00810
Review Name: GRADING
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/01/2002 | JIM TATE | ENGINEERING | REVIEW | Denied | Please include a response letter with the next submittal that states how all engineering and flood plain comments have been addressed. 1. A copy of the stamped, approved Development Plan must be included with the submittal. 2. The Drainage Report states that Miracle Mile street flow progresses westward within street gutters. The street elevation is 2310. The driveway elevation appears to be 2310.2. Since the driveway is lower than top of curb street flow will enter the property. Please revise the Drainage Report to address this offsite flow. |
04/01/2002 | MSTPAUL1 | NPDES | REVIEW | Passed | |
04/01/2002 | JOE LINVILLE | NPPO | REVIEW | Approved | Exc. LUC 3.8.3.5.E |
04/01/2002 | JAMES TATE | FLOODPLAIN | REVIEW | Denied | See Engineering folder for comments. |
04/01/2002 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/02/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |