Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T02BU00719
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2002 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | 1. Demonstrate compliance with IBC 2000 local amendment, Section 14 (Setbacks) in order to assure a minimum of 2' between property line and toe of slopes. 2. Provide written confirmation/commitment with rezoning condition # 4 (see sheet 4, app'd Development Plan. These items were discussed with Ed Roll (PM). 3. Provide site/administrative address on plan. |
| 03/13/2002 | DWILLIA1 | ZONING | REVIEW | Denied | per PGehlen |
| 03/13/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 03/14/2002 | PATRICIA GILBERT | NPPO | REVIEW | Denied | A pre-permit inspection is required to schedule please call 791-5550, ext. 140. |
| 03/18/2002 | DENNIS OSTMEYER | NPDES | REVIEW | Denied | 1. Give correct Swan Road alignment in SWPPP location map. 2. Provide a SWPPP that addresses the activities and conditions that will occur during clearing, grubbing and stockpiling. Ensure that required certifications are signed and that a Notice of Intent is filed with the appropriate agencies. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/19/2002 | LISA LESNY | OUT TO CUSTOMER | Completed |