Permit Number: T02BU00582
Parcel: 13303315D

Review Status: Completed

Review Details: GRADING

Permit Number - T02BU00582
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2002 PATRICIA GILBERT NPPO REVIEW Denied An approved site, landscape and preservation plan is required prior to approval. In addition a pre-permit native plant preservation inspection is required. To schedule please call 791-5550 ext. 140.
06/17/2002 ANY ENGINEERING REVIEW Denied To: Wayne E. Swan, P.E. Intertech
6089 E. Grant Rd.


SUBJECT: Tag Elementary School,
Grading plan T02BU00582 (Second Review)
T14S, R15E, Section 2


RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading plan:


1. The Grading plan along with the Site plan will be approved when the following condition is met: The Old Pueblo Archaeology Center's test excavation and preservation plan has been accepted. You must notify adjacent property owners of this decision; final decision is subject so comments from the affected neighbors. A copy of your notification should also be sent to the Development Services Director (Ernie Duarte) and the Ward 2 council office.

Drainage report:

1. The drainage report is approved.

If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us
Paul Machado
Senior Engineering Associate
06/17/2002 ANY FLOODPLAIN REVIEW Denied
06/19/2002 LOREN MAKUS NPDES REVIEW Approved
06/19/2002 MICHAEL ST. PAUL ZONING REVIEW Denied See comments for Engineering and Floodplain.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2002 MONICA VALDEZ OUT TO CUSTOMER Completed