Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2002 JIM TATE ENGINEERING REVIEW Denied The following items must be revised or added to the Grading Plan. Please include a letter with the next submittal addressing how all the engineering and flood plain comments have been addressed.

1. Site Plan approval is required prior to approval of the Grading Plan. Please see Site Plan comments dated March 8, 2002. Changes to the Site Plan must be reflected on the Grading Plan. Changes to the Site Plan could result in additional Grading Plan comments.

2. Keynote 28 specifies a 36" protective barrier around the basin. This must be 42". (Stormwater Detention/Retention Manual, 3.6.2)
03/08/2002 JIM TATE FLOODPLAIN REVIEW Denied See Engineering.
04/02/2002 JOE LINVILLE NPPO REVIEW Approved Small site w/ only 6 PNP's: 3 to be preserved, and 1 transplant, and 2 mitigation plants, see landscape plan.
04/04/2002 MVALDEZ1 NPDES REVIEW Needs Review
04/04/2002 MVALDEZ1 ZONING REVIEW Needs Review