Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE ONLY
Permit Number - T02BU00513
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/25/2002 | JIM EGAN | FIRE | REVIEW | Denied | 1. AUTO PARTS STORAGE NOT PERMITTED IN S-2 OCCUPANCY. 2. PROVIDE VERFICATION THAT EXISTING FIRE SPRINKLER SYTEM IS DESIGNED TO PROTECT RACK/SHELF STORAGE IN EXCESS OF 12 FEET STORAGE HEIGHT. |
| 03/06/2002 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/19/2002 | DELMA ROBEY | OUT TO CUSTOMER | Completed |