Permit Number: T02BU00235
Parcel: 11942002C

Review Status: Completed

Review Details: REVISION

Permit Number - T02BU00235
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2003 JIM TATE ENGINEERING REVIEW Denied DATE: June 4, 2003
ACTIVITY NUMBER: T02BU00235
PROJECT NAME: Charity Tabernacle Church
PROJECT ADDRESS: 4503 S. Mission
PROJECT REVIEWER: James C. Tate, P.E.

The following items must be revised or added to the Grading Plan. Please include a letter with the next submittal addressing how all the engineering and floodplain comments have been addressed.

Resubmittal Required: Grading Plan

Grading Plan

1. A copy of the stamped approved Site Plan (as revised) must be included with the Grading Plan submittal.

2. A Flood Use Permit is required prior to Grading Plan approval.

3. The revised Site Plan is currently in the review process. Any changes made to the Site Plan must be reflected on the Grading Plan. The Site Plan and Grading Plan must match.

4. Grading in excess of 5,000 yards must be performed in accordance with the approved plan prepared by a Registered Professional Civil Engineer. The proposed Grading Plan must be stamped and signed by a Civil Engineer. IBC Chapter 36 Section 9.3.

5. Place a note on the plan that all exposed cut and fill slopes will be revegetated or protected by constructed means, such as riprapping or retaining walls. DS 9-04.3.1.B.5

6. Roadway profile 2 on Sheet 4 of the Grading Plan shows a grade break in the middle of the intersection of the road and the new parking area. The road north of the grade break is at 14.41%. The new parking lot grade is specified as 4% Show the transition grades. It might be prudent to redesign the roadway so that this grade break does not occur in the intersection (for safety purposes).
06/11/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
6/11/2003
Zoning may not review and approve grading plans until Engineering does.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2003 LISA LESNY OUT TO CUSTOMER Completed
07/07/2003 ANGIE SHOFFSTALL REJECT SHELF Completed