Permit Number: T01OT00849
Parcel: 13217141A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01OT00849
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2002 PATRICIA GEHLEN ZONING REVIEW Denied
02/20/2002 JAMES TATE FLOODPLAIN REVIEW Denied See Engneering comments.
02/20/2002 JIM TATE ENGINEERING REVIEW Denied The following items must be revised or added to the Site Plan and Drainage Report. Please include a response letter with the next submittal that states how all the engineering and flood plain comments have been addressed.

The Drainage Report was reviewed for Site Plan purposes only.

A Flood Use Permit must be obtained prior to Grading Plan approval.

1. A previous comment stated that sidewalks must be physically separated from any vehicular travel lane by means of curbing, railings, barriers or other means. Section A-A on the plan shows the sidewalk not separated from the driveway. It also shows this sidewalk with a cross slope of 3%. Sidewalk cross slopes are limited to a maximum of 2%. Please correct the plan. (DS 3-01.3.3.B.5 & DS 3-01.4.1.D.1)

2. The response to Drainage Report comment 4 (CMG Drainage response letter dated January 25, 2002) says that the finished floor elevation of the east building is 1 ft. above the flow line of the east driveway and .6 ft. above the 100 yr. WSEL of the east driveway. It also says that the finished floor elevation of the west building is located 1 ft. above the 100 yr. WSEL of the drainageway. Please show the finished floor on Sections A-A, B-B, and C-C.
02/20/2002 JIM TATE SANITATION REVIEW Approved
02/26/2002 JOE LINVILLE LANDSCAPE REVIEW Denied The Landscape plan may require revision to comply with Native Plant Preservation requirements. See NPPO comments. DS 2-15.3.5
02/27/2002 JOE LINVILLE NPPO REVIEW Denied The Native Plant Preservation application for exception is not
approved due to the presence of protected native plants on the site. Please contact Joseph Linville for additional information. DS 2-15.2.0

Final Status

Task End Date Reviewer's Name Type of Review Description
03/04/2002 MONICA VALDEZ OUT TO CUSTOMER Completed