Permit Number: T01OT00223
Parcel: 12003085B

Review Status: Stopped

Review Details: RESUBMITTAL

Permit Number - T01OT00223
Review Name: RESUBMITTAL
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2002 EROSE1 BUILDING-RESIDENTIAL REVIEW Stop 2000 IRC RESIDENTIAL CHECKLIST

Date: 12-17-01
Re: Project No.T01OT00223 SECOND REVIEWED 03-29-02

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter backcheck time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating the action taken.

SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical, Model Energy and Electrical codes. All code references are to the 2000 IRC. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLAN:

1. Provide all window sizes and types, and designate the operable portion of windows, as well as the locations of tempered glass per R308.4.

2. Show compliance with R310 providing egress from bedrooms: 4030 WITH STANDARD LINTEL HEIGHT DOES N'T GIVE YOU 44" SILL HEIGHT -CLARIFY

a. Maximum sill height of 44".
b. Minimum net clear area of opening of 5.7 s.f.
c. Minimum net clear dimensions of opening of 24" height by 20" width.

3. EMERGENCY LIGHTING MUST BE LIGHTING EXIT TRAVEL

4. INDICATE RAMP ON SECOND EXIT. INDICATE 1/12 SLOPE ON ALL RAMPS

5. INDICATE EXIT SIGNS ON REQUIRED EXIT DOORS.

6. FLOOR PLAN LAYOUT SPRINKLE SYSTEM DOESN'T MATCH FLOOR PLAN.- REMODELING ???


REVIEWED BY REYES ARVAYO 791-5550 EXT. 113

Final Status

Task End Date Reviewer's Name Type of Review Description
03/12/2002 ANY APPROVAL SHELF Stopped
03/12/2002 ANY OUT TO CUSTOMER Stopped
03/12/2002 ANY REJECT SHELF Stopped