Permit Number: T01OT00108
Parcel: 121100080

Address:
4734 E EDISON ST

Review Status: Completed

Review Details: C OF O

Permit Number - T01OT00108
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2001 DAN CASTRO ZONING REVIEW Approved
04/25/2001 CHUCK STEPHENSON SIGNS REVIEW Approved
05/31/2001 DAVE WILLETT BUILDING-COMMERCIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T01OT00108

05/31/01

PLEASE ADDRESS THE FOLLOWING COMMENTS. RESUBMIT TWO SETS OF CORRECTED PLANS. SUBMIT A COPY OF THIS LETTER , NOTING THE DETAIL AND OR SHEET WHERE THE CORRECTION MAY BE FOUND.


GENERAL REQUIREMENTS

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS SHALL BE RETURNED.

2. DETAILS, DATA AND INFORMATION PROVIDED BY THE DEVELOPMENT SERVICES DEPARTMENT SHALL NOT BE INCLUDED BY REFERENCE OR ATTACHMENT ONLY. THE DATA MUST BE DELINEATED ON THE DRAWINGS BY NOTES OR GRAPHICS AS PART OF THE ORIGINAL TRACINGS OR MASTERS.

3. PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

4. ALL PLANS SHALL BE LEGIBLE AND NO SCALE SMALLER THAN 1/4"=1'-0" SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS -MINIMUM 3/8" SCALE.


MISCELLANEOUS

1. REFER TO THE ATTACHED HAND OUT ON THE REQUIREMENTS NEEDED TO BE SHOWN ON THE DRAWINGS.

2. PROVIDE A FLOOR PLAN SHOWING THE BUILDING RELATED REQUIREMENTS.

3. PROVIDE A ELECTRICAL PLAN SHOWING THE LAYOUT OF THE SMOKE DETECTORS, EMERGENCY LIGHTING AND THE REQUIRED GFCI OUTLETS IN THE KITCHEN AND BATHROOMS. ALL ELECTRICAL WORK IS TO BE DONE PER THE NATIONAL ELECTRICAL CODE 1999 EDITION.





IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WILLETT: 791-5550; EXT. 110

Final Status

Task End Date Reviewer's Name Type of Review Description
06/01/2001 MONICA VALDEZ OUT TO CUSTOMER Completed