Permit Number: T01CM06030
Parcel: 116122730

Address:
1315 W SONORA ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T01CM06030
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2002 MVALDEZ WWM REVIEW Needs Review
12/13/2001 DAN CASTRO NPPO REVIEW Passed
12/13/2001 DAN CASTRO ZONING REVIEW Approved
12/13/2001 PAUL MACHADO FLOODPLAIN REVIEW Approved
12/27/2001 REYES ARVAYO BUILDING-RESIDENTIAL REVIEW Denied 2000 IRC RESIDENTIAL CHECKLIST

Date: 12-27-01
Re: Project No. T01CM06030

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed.
SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical, Model Energy and Electrical codes. All code references are to the 2000 IRC. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.


SITE PLAN

1. Indicate the location , electric on the property, and where they enter the building . Doesn't match elect. Plan.

FOUNDATION PLAN:

1. Note on the drawings the allowable soil bearing pressure used in the design of the footings, or state that the assumed value of 1500 psf is being used, per Table R401.4.1, a soils report is not required. It is up to the designer/homebuilder to be aware of the soil conditions of the site. If soil testing has been done, a copy of the soils report shall be submitted with the construction plans, and the foundation design shall reflect soils report recommendations.

2. Dimension the stem wall thickness, footing width thickness and depth into undisturbed soil for each footing type and condition, per Table R403.1.
- 16" minimum; conventional light frame/wood/metal

3. All foundation hold downs and anchor bolt spacing for shear walls shall be specified and located. Brace panels 2'-8"

FLOOR PLAN:

1. Label all rooms and spaces - Laundry walls?

2. Appliances installed in garages shall be mounted on platforms at least 18" above the floor, per M1307.3 .Clarify if laundry is enclose .

3. Delete note about common wall.

STRUCTURAL PLANS:

1. Specify design criteria on plans: Values for floor dead load and live load, roof dead load and live load.

2. Interior beam 6x10 inadequate -also must have full bearing- 2x4 interior wall?

3. 4x10 beam in carport inadequate -

4. Provide complete roof framing plans. Show size, spacing and span of all framing members, rafters, beams,


5. Detail connections and cross-reference to the foundation and framing plans:
interior Beam to post

ELEVATIONS:

1. For thin-coat stucco systems over foam board, note and specify the ICBO evaluation report number, system name and manufacturer. Note and specify the vapor barrier.


MECHANICAL PLANS:

1. Gas appliances shall comply with Chapter 17 combustion air requirements. Detail how this is achieved. Both furn and w/h.

2. Gas meter doesn't match site plan developed length?

ELECTRICAL PLANS:

1. Note the location, type and amperage of the panel. Note the grounding and bonding method.

2. Submit riser diagram. Min. 8' clearance above roof required on drop. Indicate how you plan on installing riser.-doesn't match site plan.

MODEL ENERGY CODE:

1. Provide Energy Calculations per IECC, or comply with IRC Chapter 11.

REVIEWED BY REYES ARVAYO 791-5550 EXT. 110

Final Status

Task End Date Reviewer's Name Type of Review Description
01/07/2002 MONICA VALDEZ OUT TO CUSTOMER Completed