Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM06006
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/09/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
01/09/2002 | TOM CLARK | WATER | REVIEW | Approv-Cond | |
01/14/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/15/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E-1 1) The 75-kVA transformer lacks proper work clearance. See 99NEC 110-26 2) Provide a catalog cut with the model number for keynote 18. 3) Contained within chapter 3 of the paint booth submittal are the booth elevations. The elevations depict a man door on the side view. The 99NEC article 516-2(b)(4) requires all electrical within a 3' radius of any opening to be rated for a class 1 division 2 area. Clearly show all openings on the booths and delineate the 3' boundaries on the plan. Note page M-1 describes the booth as ETL report #570265, which corresponds, with ULTRA paint booth. |
01/16/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | |
01/16/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | |
01/23/2002 | GERRY KOZIOL | WWM | REVIEW | Passed | |
12/12/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
12/12/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved |