Permit Number: T01CM06006
Parcel: 10408086C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM06006
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2002 JIM EGAN FIRE REVIEW Approved
01/09/2002 TOM CLARK WATER REVIEW Approv-Cond
01/14/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
01/15/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E-1
1) The 75-kVA transformer lacks proper work clearance. See 99NEC 110-26
2) Provide a catalog cut with the model number for keynote 18.
3) Contained within chapter 3 of the paint booth submittal are the booth elevations. The elevations depict a man door on the side view. The 99NEC article 516-2(b)(4) requires all electrical within a 3' radius of any opening to be rated for a class 1 division 2 area. Clearly show all openings on the booths and delineate the 3' boundaries on the plan.
Note page M-1 describes the booth as ETL report #570265, which corresponds, with ULTRA paint booth.
01/16/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied
01/16/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
01/23/2002 GERRY KOZIOL WWM REVIEW Passed
12/12/2001 DAN CASTRO ZONING REVIEW Approved
12/12/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2002 TGRIFFU1 OUT TO CUSTOMER Completed