Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM06006
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/09/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/09/2002 | TOM CLARK | WATER | REVIEW | Approv-Cond | |
| 01/14/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/15/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E-1 1) The 75-kVA transformer lacks proper work clearance. See 99NEC 110-26 2) Provide a catalog cut with the model number for keynote 18. 3) Contained within chapter 3 of the paint booth submittal are the booth elevations. The elevations depict a man door on the side view. The 99NEC article 516-2(b)(4) requires all electrical within a 3' radius of any opening to be rated for a class 1 division 2 area. Clearly show all openings on the booths and delineate the 3' boundaries on the plan. Note page M-1 describes the booth as ETL report #570265, which corresponds, with ULTRA paint booth. |
| 01/16/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | |
| 01/16/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | |
| 01/23/2002 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 12/12/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 12/12/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/23/2002 | TGRIFFU1 | OUT TO CUSTOMER | Completed |