Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T01CM05822
Review Name: REVISION
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/22/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | I spoke with the electrical insp. He indicated the plan should accurately reflect the one-line service diagram and panel schedules. The plan submitted does not represent the actual field conditions. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/22/2002 | ELAINE ROSE | OUT TO CUSTOMER | Completed |