Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T01CM05822
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | I spoke with the electrical insp. He indicated the plan should accurately reflect the one-line service diagram and panel schedules. The plan submitted does not represent the actual field conditions. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/22/2002 | ELAINE ROSE | OUT TO CUSTOMER | Completed |