Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM05789
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/29/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 11/29/2001 | MATT FLICK | FLOODPLAIN | REVIEW | Approved | |
| 11/30/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/04/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | |
| 12/04/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 12/04/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/05/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.1500 watt radiant heat should be on a seperate circuit. 2.Indicate the refridgerator location on the electrical plan. 3.Indicate the hood circuit (not to be on the kitchen small appliance circuit). 4. Remove the reference to 400 amp main breaker at panel schedule or explain. 5.Indicate the refridgerator circuit on the electrical plan. 6.Provide the size of the service lateral conductors on the plans along with the combined calculated load that are utilizing this service. 7.Indicate the double oven location on the electrical plan. 8.Add receptacle at bedroom #1 next to rear door (hinge side),and relocate receptacle as shown on the plans (see clouded arrow). |
| 12/10/2001 | TOM CLARK | WATER | REVIEW | Approved | |
| 12/12/2001 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/21/2001 | TAMI ACHONG | OUT TO CUSTOMER | Completed |