Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T01CM05607
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2002 JIM EGAN FIRE REVIEW Denied 1. FIRE SPRINKLER DESIGN CRITERIA INCORRECT. SHT.FP1.1
2. PROVIDE WATER SUPPLY INFORMATION SHT. FP1.1 STATIC__PSI RESIDUAL__PSI FLOW__GPM.
3. FIRE SPRINKLER RISER DETAIL INCORRECT. SHT FP1.1
01/02/2002 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
01/08/2002 PATRICIA GEHLEN ZONING REVIEW Denied
01/09/2002 DROBEY FLOODPLAIN REVIEW Needs Review
01/09/2002 DROBEY WWM REVIEW Needs Review
11/15/2001 INGA DAVIDSON WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2002 DELMA ROBEY OUT TO CUSTOMER Completed