Permit Number: T01CM05582
Parcel: 12702276A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM05582
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
03/18/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied
03/25/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied Plans are incomplete thus this represents a partial review only. A complete review will commence subsequent to the second submittal.
1) Provide fixture schedule, include fixture loads in VA for each fixture. Provide catalog cuts and fixture order numbers for all exterior fixtures. See www.cityoftucson.org/dsd for City lighting ordinance.
2) Provide a lighting model energy calculation based upon the 1998 IECC. The maximum W/ft2 is 1.7 for an office occupancy.
3) Provide fault current calculations. Begin analysis with TEP AFC. Note: Fault attenuation via the fuse requires a fully listed/labeled series rated system to be specified. Provide the component short circuit current rating for the panelboards.
4) Provide conduit, conductor, disconnect, and fuse size for all HVAC equipment.
5) Provide GFCI maintenance receptacle within 25' of HVAC equipment.
6) The service lateral must be a minimum of 3 parallel sets.
03/26/2002 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
03/27/2002 TOM CLARK WATER REVIEW Passed
03/27/2002 JIM EGAN FIRE REVIEW Denied
04/03/2002 TACHONG1 ZONING REVIEW Needs Review
04/03/2002 TACHONG1 FLOODPLAIN REVIEW Needs Review
04/03/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2002 TAMI ACHONG OUT TO CUSTOMER Completed