Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM05502
Parcel: 115151540

Address:
624 W RILLITO ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01CM05502
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2002 JIM EGAN FIRE REVIEW Approved
01/14/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied
01/14/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
01/15/2002 PHIL SEADER BUILDING-COMMERCIAL REVIEW Approved
01/17/2002 PATRICIA GEHLEN ZONING REVIEW Approved
01/17/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) OK
2) The service lateral is customer provided. Provide a design.
NEW: Remove the ground wire. It is bonded to the neutral at both the service
and the transformer effectively putting it in parallel with the neutral.
3) Provide TEP AFC at the transformer secondary to begin your required fault current analysis. Unless an UL listed series rated system is specified fuse let through charts cannot be utilized.
NEW: TEP published data indicates a minimum of 27,800 amps. Provide fault
verification from the utility.
4) OK
5) OK
6) Provide a 1998 IECC lighting budget analysis.
NEW: Provide the analysis.
7) Circuits A5, A7, and A17 serve 3 rows of lighting all connected to 1 pair of 3 way switches. Clarify how this is possible.
NEW: The design has not changed.
8) Provide disconnects, overload, and short circuit protection per 99NEC parts C, D, and J for all motors.
NEW: The design has not changed
9) OK
10) OK
11) Clarify what will be stored within the warehouse. Provide a letter from the owner (on their letterhead) or provide a letter sealed and signed by the architect or engineer of record.
NEW: A descriptive letter was not included in the submittal.
12) Include the plans I have already reviewed along with your next submission.
NEW: Please comply.
13) OK
NEW COMMENTS FROM SECOND REVIEW
1) The electrical notes on page E1 reference CLASSIFIED areas and HANGERS. Please clarify.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/20/2002 TGRIFFU1 OUT TO CUSTOMER Completed