Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM05477
Parcel: 141015610

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T01CM05477
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2001 PETER MCLAUGHLIN ZONING REVIEW Approved
11/05/2001 PETER MCLAUGHLIN NPPO REVIEW Passed
11/05/2001 BLANCA ESPINO FLOODPLAIN REVIEW Approved
11/07/2001 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T01CM05477

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. ALL FOUNDATION HOLD-DOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED AND
LOCATED.-----------PAHD42 CANNOT BE USED WITHIN 8" OF A CORNER----A HPAHD22 CAN AND GIVES THE SAME VALUES-----WRONG AT GARAGE FRONT

FLOOR PLANS:

1. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

STRUCTURAL PLANS:

1. LANDING MISSING FOR SPIRAL STAIR CASE. INDICATE GUARDRAIL AT LANDING.

2. BEAM #1 WILL NEED STRUCTURAL CALCS. -----PRESCRIPTIVE METHOD DOES NOT COVER THIS BEAM

3. PRESCRIPTIVE METHOD DOES NOT COVER LEDGERS------PROVIDE CALCS. FOR SIZING

4. MISSING TO MANY THINGS ON STRUCTURAL TO COMPLETE STRUCTURAL REVIEW:
1. NUMBER AND SIZE OF SCREWS AT CONNECTIONS
2. LATERAL CALCS. FOR SHEAR WALLS
3. HANGERS ARE FOR WOOD FRAME NOT STEEL
4. CALCS. PROVIDED DO NOT MATCH DETAILS THAT ARE STAMPED
5. HAVE ENGINEERS STAMP AND REVIEW ALL PAGES IN THEIR AREA
6. AS PER PHONE CONVERSATION I HAVE STOPPED REVIEW, THERE MAY BE OTHER ITEMS, HAVE ENGINEERS DO A COMPLETE REVIEW BEFORE RESUBMITTAL

MECHANICAL PLANS:

1. IF THE HEATING OR AIR CONDITIONING EQUIPMENT IS LOCATED IN THE ATTIC, SHOW LOCATION OF ACCESS,
CATWALK AND WORKING PLATFORM. SHOW PROVISIONS FOR AND ROUTE OF SECONDARY CONDENSATE
DRAIN PER M1305.1.3.

ELECTRICAL PLANS:

1. PROVIDE COMPLETE PLANS FOR PV SYSTEM OR INDICATE THAT A SEPARATE PERMIT WILL BE REQUIRED FOR PV SYSTEM

2. INDICATE THE LOCATION OF CONVENIENCE OUTLET AND LIGHT SWITCH FOR ATTIC HEATING AND AIR
CONDITIONING EQUIPMENT PER E3801.11 AND E3803.4.

3. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

4. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 112
11/28/2001 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2001 DELMA ROBEY OUT TO CUSTOMER Completed