Permit Number: T01CM05386
Parcel: 111070020

Address:
3455 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM05386
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2001 JIM EGAN FIRE REVIEW Approved
11/27/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied
11/27/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
11/30/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied GENERAL COMMENTS
1) Provide all exterior fixture cuts along with their catalog numbers. The catalog numbers must correspond with the fixture schedule.
2) Provide IECC lighting budget calculations. Note this facility is allowed 1.7W/FT2 and appears to comply.
3) Return the plans I have already reviewed along with your next submission. Failure to do so will result in an extended turnaround time as I need the original plans for comparative purposes.
E1.1
1) Revise the fixture schedule on page E1.1 and E4.1 to reflect the LSI submittal intended to replace the B fixtures.
2) Circuit B-27 serves a direction sign however on page E2.2 it is shown as a spare in the panel.
E2.1
1) Provide a service lateral design. Include conductor and conduit size, quantity, number of parallel sets, and conductor and conduit type.
2) The utility published fault at the secondary terminals of their transformer is 55,600 amps. Assuming a 15' run of parallel copper conductors in PVC the fault at the service is approximately 49.2 kA.
3) Revise fault calculation number 2 to reflect 1/0 as opposed to a number 1 conductor.
4) Clarify that the "Extension Table" is included in the load summary.
E3.1
1) Circuit A-21 and A-42 (items #10 and #10A in the equipment schedule) require a minimum 30 amp receptacle. 99NEC 210-21(b)(1)
2) Circuit A-14 which serves a 3.5 kVA drink system ( item 6 in the equipment schedule) cannot be served by a duplex receptacle.
3) Change the 1996 422-25 reference regarding appliance disconnects to 99NEC 422-31(b).
E4.1
1) Provide fixture cuts and catalog numbers for key notes #2 fixture.
2) Revise the B and B1 descriptions in the fixture schedule to accurately reflect the substituted fixture.
E5.1
1) RTU-2 should be served by circuit B-32,34,36 and from panel A as shown.
E7.1
1) Revise the receptacle description in detail 4 for the menu board. The receptacle should be a L5-20 as the breaker serving it is rated 20amps. 99NEC 210-21(b)(1)
12/21/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied See comments attached to application.
12/28/2001 MICHAEL ST. PAUL ZONING REVIEW Denied
12/28/2001 MSTPAUL FLOODPLAIN REVIEW Denied
12/28/2001 MSTPAUL WWM REVIEW Denied
12/31/2001 RONALD ENGELKES WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2002 TAMI ACHONG OUT TO CUSTOMER Completed