Permit Number: T01CM05294
Parcel: 130070070

Review Status: Completed

Review Details: SITE

Permit Number - T01CM05294
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2001 JIM EGAN FIRE REVIEW Approved
11/16/2001 DAN CASTRO NPPO REVIEW Passed
11/16/2001 DAN CASTRO LANDSCAPE REVIEW Passed
11/16/2001 DAN CASTRO ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/DEVELOPMENTSTANDARD

1. Please note the existing and proposed use along with the applicable development designator and any "subject to" sections on the site plan. This review is based on the principal use of "Trade Service and Repair, Major", development designator "33", subject to: Sec. 3.5.4.15 with a less than 25% expansion of the building area. If the principal use of this site differs, additional comments may be required upon resubmittal of the site plan.
D.S. 2-02.2.1.A.31

2. List the legal description of the subject property on the site plan. D.S. 2-02.2.1.A.2

3. Add a location map.D.S. 2-02.2.1.A.4

4. List the height of all existing buildings, overhangs, structures, and canopies on the site plan. D.S. 2-02.2.1.A.6

5. List the adjacent zoning classifications on the site plan. Properties to the north of the subject property are zoned C-3.
D.S. 2-02.2.1.A.28

6. If applicable, provide a detail of proposed free standing signage and outdoor lighting on the site plan.
D.S. 2-02.2.1.A.13; D.S. 2-02.2.1.A.25

7. Dimension the right-of-way for Juarez Avenue.
D.S. 2-02.2.1.A.19

8. If applicable, all existing or proposed easements must be shown on the plan including width, type, and recording docket and page reference.
D.S. 2-02.2.1.A.20

9. List the gross site area on the site plan.
D.S. 2-02.2.2.A.1

10. List the floor area ratio calculation.
D.S. 2-02.2.2.A.3

11. Add cumulative building area expansion calculation to site plan. Previous approved site plan indicates a 2001.5 square foot addition in 1989. The building addition under this permit is 197 square feet, totaling (2001.5 + 197 = 9,151.5 divided by 10,158) = 24.02% expansion to date, not 12.6% as is shown on plan.
D.S. 2-02.2.2.A.6

12. Minimum font size is 12 for all letters and numbers on site plan.
11/30/2001 BLANCA ESPINO FLOODPLAIN REVIEW Approved
11/30/2001 BLANCA ESPINO ENGINEERING REVIEW Denied 1. Please show a location map with a north arrow, property description and use a scale of 3" = 1 mile.

2. Please label lot with bearings.

3. Show all existing and future sight visibility triangles on Juarez St. onto Alvernon Way and all entrances into parking lot.

4. Clearly identify vehicular and pedestrian circulation.

5. Please show location, type, size and height of existing and proposed signage, if applicable.

6. Fully dimensioned loading space(s) and maneuvering area(s), if applicable.

7. Please show drainage patterns, proposed finish floor elevation(s) and finish grades.

8. Street names need to be labeled private or public and please add correct extension to street name such as; Street, Road, Blvd..... and so on.

9. Please dimension from street monument lines to existing and proposed curbs, sidewalks, driveways and utility lines.

10.Please show refuse container location, size and access thereto fully dimensioned, as per D.S. 6-01.3.0 thru
6-01.10.0
11/30/2001 BLANCA ESPINO SANITATION REVIEW Denied
12/03/2001 PHIL SEADER HANDICAP-SITE REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2001 CINDY AGUILAR OUT TO CUSTOMER Completed