Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T01CM05294
Parcel: 130070070

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM05294
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2001 JIM EGAN FIRE REVIEW Approved
10/25/2001 MIKE BERGHUIS FLOODPLAIN REVIEW Approved
10/31/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
10/31/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
11/05/2001 RANDY SCHULER BUILDING-COMMERCIAL REVIEW Denied
11/08/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) Provide 2 sets of plans.
2) Unless the booth is fully listed and labeled by a 3rd party OSHA approved testing laboratory and all of the electrical on the booth is factory installed provide a complete electrical design. If the booth is properly listed and factory wired provide a note of clarification on the plan.
If the booth is properly listed and factory wired provide the location of the disconnects, switches, and control panels. This information is necessary to verify proper working clearances are maintained.
3) The booth opening appears to be closer than 3' to the main service entrance equipment. See page A21 for a scaled drawing of booth.
4) Provide a complete electrical design for the new office addition.
5) It appears the main service disconnect is double lugged. Provide the conductor size and length of the feeder serving the front offices.
6) Show the openings in close proximity to the booth on the electrical plan. See page A21 for necessary details.
12/04/2001 MICHAEL ST. PAUL ZONING REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2002 MONICA VALDEZ OUT TO CUSTOMER Completed