Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2001 PHIL SEADER HANDICAP-SITE REVIEW Approved
10/26/2001 JIM EGAN FIRE REVIEW Approved FIRE HYDRANTS REQUIRED. SUBMIT APPROVED WATER PLAN.
11/07/2001 PETER MCLAUGHLIN ZONING REVIEW Approved
11/15/2001 JOE LINVILLE NPPO REVIEW Approved
11/15/2001 JOE LINVILLE LANDSCAPE REVIEW Approved
12/05/2001 BLANCA ESPINO FLOODPLAIN REVIEW Approved
12/05/2001 BLANCA ESPINO ENGINEERING REVIEW Approved D.S. 2-02.2.1 Site Plan
1. Please relocate Refuse enclosure. Also add two post on the inside of each side wall of enclosure. Demonstrate Solid Waste Vehicle maneuverability.

Drainage Report
1. The Site/Grading & Paving Plan in your Drainage Report does not show scuppers on the original Site Plan. Please reflect the new changes on the Site Plan.

2. Apply the appropriate Safety Factor for the curb inlets as per SMDDFM page 10.24, 10.6.9 Clogging

3. As per the approved Tentative Plat/Drainage Report S99-053 it demonstrates drainage flow direction to the northwesterly channel of the site for Lot 2. Please verify that the northeasterly earthen channel has the capacity to hold the on-site flow for Lot 2.

4. Please show details of down spout and splash guard.
12/05/2001 BLANCA ESPINO SANITATION REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/03/2001 TAMI ACHONG OUT TO CUSTOMER Completed