Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2002 JIM EGAN FIRE REVIEW Approved
09/24/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide a civil site plan with FFE, UP stream MH Rim Elev., sewer line size and slope. 2. Waste fixture units for a tank WC is 6 fu ea , total fixture units is 34. 3. Gas line going to the north units is indicated as 1/2", needs to be 3/4". 4. Provide a trap primer for the FD in toilet rm #3.
09/24/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Concrete pads need to be 6" Sec304.8IMC2000. 2. Show on the plan how the mechanical design complies with Chapter 4 and 5 IMC 2000.
09/24/2002 HOLLY PEARCE WATER REVIEW Approved
09/30/2002 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied q Indicate use for second floor. Note: If area is to be used for storage indicate 125 pound live load as per Table 1607.1 IBC and revise structural calculations.

q Provide Structural calculations and plans for proposed metal building structure.

q Fire barrier wall openings exceeds 25% of maximum aggregated width of wall allowed. Reference section 706.6 IBC. Revise plans by reducing openings or provide 1 hour opening protection.

q Doors may not encroach more than ½ the minimum width of the hallway. Reference section 1003.2.3. Revise plans in order to obtain minimum egress widths.

q Stair treads and risers to have a minimum of an 11 inch run and a maximum of 7 inch rise. Reference section 1003.3.3 IBC.

q Include handrail locations, height, and continuity. Reference sections 1003.3.3.11, 1003.3.3.11.1, and 1003.3.3.11.3 IBC

q Provide listing for fire resistive application at main frame.

q Fire Barrier wall to have continuos 1 hour protection from floor to roof deck. See loss of protection at second floor intersection. Reference section 706.4 IBC
10/02/2002 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.maintain a 10 pt. (min.) font on plans 2.all wiring methods to comply with art. 511 ( 1999 N.E.C.). 3. the second set of electrical plans are not ledgible. Please provide a second set of electrical plans that are easy to follow.
10/11/2002 GERRY KOZIOL WWM REVIEW Denied Needs to show location of connection to public sewer.
10/23/2002 MATT FLICK FLOODPLAIN REVIEW Approved Subject to Floodplain Use Permit No. T02OT00681.
10/28/2002 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
10/28/2002
Zoning will review once the building plans are approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/29/2002 ELAINE ROSE OUT TO CUSTOMER Completed