Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T01CM05242
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 09/24/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide a civil site plan with FFE, UP stream MH Rim Elev., sewer line size and slope. 2. Waste fixture units for a tank WC is 6 fu ea , total fixture units is 34. 3. Gas line going to the north units is indicated as 1/2", needs to be 3/4". 4. Provide a trap primer for the FD in toilet rm #3. |
| 09/24/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Concrete pads need to be 6" Sec304.8IMC2000. 2. Show on the plan how the mechanical design complies with Chapter 4 and 5 IMC 2000. |
| 09/24/2002 | HOLLY PEARCE | WATER | REVIEW | Approved | |
| 09/30/2002 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | q Indicate use for second floor. Note: If area is to be used for storage indicate 125 pound live load as per Table 1607.1 IBC and revise structural calculations. q Provide Structural calculations and plans for proposed metal building structure. q Fire barrier wall openings exceeds 25% of maximum aggregated width of wall allowed. Reference section 706.6 IBC. Revise plans by reducing openings or provide 1 hour opening protection. q Doors may not encroach more than ½ the minimum width of the hallway. Reference section 1003.2.3. Revise plans in order to obtain minimum egress widths. q Stair treads and risers to have a minimum of an 11 inch run and a maximum of 7 inch rise. Reference section 1003.3.3 IBC. q Include handrail locations, height, and continuity. Reference sections 1003.3.3.11, 1003.3.3.11.1, and 1003.3.3.11.3 IBC q Provide listing for fire resistive application at main frame. q Fire Barrier wall to have continuos 1 hour protection from floor to roof deck. See loss of protection at second floor intersection. Reference section 706.4 IBC |
| 10/02/2002 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.maintain a 10 pt. (min.) font on plans 2.all wiring methods to comply with art. 511 ( 1999 N.E.C.). 3. the second set of electrical plans are not ledgible. Please provide a second set of electrical plans that are easy to follow. |
| 10/11/2002 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs to show location of connection to public sewer. |
| 10/23/2002 | MATT FLICK | FLOODPLAIN | REVIEW | Approved | Subject to Floodplain Use Permit No. T02OT00681. |
| 10/28/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 10/28/2002 Zoning will review once the building plans are approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/29/2002 | ELAINE ROSE | OUT TO CUSTOMER | Completed |