Permit Number: T01CM04863
Parcel: 130056830

Address:
2853 E MENOR SV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T01CM04863
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2001 PETER MCLAUGHLIN ZONING REVIEW Approved
09/28/2001 PETER MCLAUGHLIN NPPO REVIEW Passed
09/28/2001 MIKE BERGHUIS FLOODPLAIN REVIEW Approved
10/15/2001 REYES ARVAYO BUILDING-RESIDENTIAL REVIEW Denied 2000 IRC RESIDENTIAL CHECKLIST
Date: 10-15-01
Re: Project No. T01CM04863

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed.

SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical, Model Energy and Electrical codes. All code references are to the 2000 IRC. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FOUNDATION PLAN:

1. Dimension the stem wall thickness, footing width thickness and depth into undisturbed soil for each footing type and condition, per Table R403.1.

- 19" minimum; hollow concrete/masonry

STRUCTURAL PLANS:

1. Specify design criteria on plans: Values for floor dead load and live load, roof dead load and live load.

2. Provide complete roof plans. Show size of beams, glulams, lintels.

3. Detail connections and cross-reference to the foundation and framing plans:
- Beam to existing wall

4. Indicate size of beam -between kitchen and new addition same for bedroom -and detail connection to rafters

REVIEWED BY REYES ARVAYO 791-5550 EXT. 113
10/17/2001 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/30/2001 LISA LESNY OUT TO CUSTOMER Completed