Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T01CM04846
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/28/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/05/2001 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Denied | |
| 10/12/2001 | DAN CASTRO | ZONING | REVIEW | Denied | |
| 10/17/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide available fault current at service. 2.Provide A.I.C. rating of service equipment and breakers. 3.Is the service single phase or three phase? The panel schedule contradicts itself.(also the voltage) 4.Provide cut sheets on fixtures greater than 50 watts. 5.Provide I.E.C.C. lighting calculations. 6.I can't locate circuit #4 on the electrical plan. 7.Circuit #2 is overloaded according to your information. 8.Provide a fixture schedule with the number of lamps, wattages of lamps(including the ballast) as well as the type of lamp(incandescent,fluorescent etc.). 9.Fixtures must comply with the outdoor lighting ordinance. |
| 10/17/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | |
| 10/17/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/25/2001 | INGA DAVIDSON | WATER | REVIEW | Approv-Cond | |
| 10/25/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 10/31/2001 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/31/2001 | TAMI ACHONG | OUT TO CUSTOMER | Completed |