Permit Number: T01CM04846
Parcel: 120086800

Address:
4762 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM04846
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2001 JIM EGAN FIRE REVIEW Approved
10/05/2001 BLANCA ESPINO FLOODPLAIN REVIEW Denied
10/12/2001 DAN CASTRO ZONING REVIEW Denied
10/17/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Provide available fault current at service.
2.Provide A.I.C. rating of service equipment and breakers.
3.Is the service single phase or three phase? The panel schedule contradicts itself.(also the voltage)
4.Provide cut sheets on fixtures greater than 50 watts.
5.Provide I.E.C.C. lighting calculations.
6.I can't locate circuit #4 on the electrical plan.
7.Circuit #2 is overloaded according to your information.
8.Provide a fixture schedule with the number of lamps, wattages of lamps(including the ballast) as well as the type of lamp(incandescent,fluorescent etc.).
9.Fixtures must comply with the outdoor lighting ordinance.
10/17/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied
10/17/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
10/25/2001 INGA DAVIDSON WATER REVIEW Approv-Cond
10/25/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
10/31/2001 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/31/2001 TAMI ACHONG OUT TO CUSTOMER Completed