Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/FLOOD
Permit Number - T01CM04776
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2001 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 09/25/2001 | PAUL MACHADO | FLOODPLAIN | REVIEW | Approved | |
| 09/25/2001 | PETER MCLAUGHLIN | NPPO | REVIEW | Passed | |
| 10/16/2001 | DAVE WILLETT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T01CM04776 10/16/01 PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. SITE PLAN: 1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM IF IT EXISTS. FOUNDATION PLANS: 1. NOTE ON PLANS: GLASS IN HAZARDOUS AREAS, ALL GLASS WINDOWS WITHIN A 24" ARC OF EITHER VERTICAL EDGE OF A DOOR SHALL BE SAFETY GLASS. IRC SEC 308 @ AZ ROOM. 2. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT. STRUCTURAL PLANS: 1. SPECIFY DESIGN CRITERIA ON PLANS. VALUES FOR ROOF DEAD LOAD AND LIVE LOAD AND SPAN OF EXISTING ROOF. ALSO SPECIFY TYPE OF EXISTING ROOF SYSTEM, IE: TRUSSES ETC. 2. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR TAPERED TJI JOISTS. 3. PROVIDE A HEADER SCHEDULE OR NOTE HEADER SIZES AT ALL BEARING OPENINGS ON FRAMING OR FLOOR PLANS. 4. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING PLANS: - POST TO SLAB @ PORCH - LEDGERS TO FRAME, FRAME TO LEDGERS @ PORCH - JOIST TO LEDGER @ PORCH - HANGER TYPES @ PORCH - HOLD DOWN LOCATIONS AND TYPE @ AZ ROOM 5. PROVIDE BRACING DETAILS AND NOTES FOR EXTERIOR FRAME WALLS AND MAIN CROSS-STUD PARTITIONS, OR USE FULLY BRACED, PER R602.10.3. A MINIMUM PANEL WIDTH OF 48" IS REQUIRED TO EFFECTIVELY BRACE THE PARTITION. SEE TABLE R602.10.3, CATEGORY "C". IF BRACING DOES NOT COMPLY, PROVIDE A LATERAL ANALYSIS OR ALTERNATE DESIGN TO BE REVIEWED BY THE PLANS EXAMINER. WIND FORCES FOR SINGLE STORY RESIDENCES SHALL USE 90 MPH, EXPOSURE "B". TWO STORY RESIDENCES OR AREAS OF HIGHER WIND SHALL USE EXPOSURE "C". MECHANICAL PLANS: 1. SHOW EXHAUST FAN LOCATIONS FOR BATHROOMS, WATER CLOSET COMPARTMENTS IN LIEU OF OPERABLE WINDOWS, PER R303.3 @ EXISTING BATHROOMS. MODEL ENERGY CODE: 1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11. MEC CHECK SOFT WARE IS AVAILABLE FOR FREE ON THE INTERNET AT www.BTS-Building Energy Codes. 2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WILLETT @ 791-5550 EXT. 110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/18/2001 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |