Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE ONLY
Permit Number - T01CM04658
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 09/18/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/18/2001 | DWILLIAM | ZONING | REVIEW | Approved | approved by C. Gross |
| 09/19/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Show on the plan how the private sewer attaches to the public sewer. Provide the size of the sewer and slope of the same on the plan. 2. The drainage fixture units are incorrect. The fixture units are to be taken from Appendix E. All design shall be based on Appendix E 1994 UPC Az. Code. |
| 09/19/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 09/20/2001 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/20/2001 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 09/19/2001 | SUE REEVES | OUT TO CUSTOMER | Completed |