Permit Number: T01CM04307
Parcel: 117050590

Address:
415 N 6TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM04307
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2001 DAVID RIVERA ZONING REVIEW Approved
09/06/2001 TOM WEIDEMAN FLOODPLAIN REVIEW Approved
09/06/2001 JIM EGAN FIRE REVIEW Denied
09/10/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
09/10/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Provide access to equipment in the attic space Per Sec306.3 IMC2000 and on the roof Per Sec306.5IMC2000. Show access to the equipment on the plan. 2. Condensate shall discharge in an approved location, not at grade outside. 3. Provide Combustion/Relief air Per Chapter 7IMC2000. 4. OSA and exhaust from the bathrooms does not comply with Sec 502.6.3.6IMC2000.
09/13/2001 INGA DAVIDSON WATER REVIEW Approved
09/24/2001 GERRY KOZIOL WWM REVIEW Approved
09/27/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
10/04/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ATTACHED TO APPLICATION.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2001 CINDY AGUILAR OUT TO CUSTOMER Completed