Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM04307
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/31/2001 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/06/2001 | TOM WEIDEMAN | FLOODPLAIN | REVIEW | Approved | |
| 09/06/2001 | JIM EGAN | FIRE | REVIEW | Denied | |
| 09/10/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/10/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Provide access to equipment in the attic space Per Sec306.3 IMC2000 and on the roof Per Sec306.5IMC2000. Show access to the equipment on the plan. 2. Condensate shall discharge in an approved location, not at grade outside. 3. Provide Combustion/Relief air Per Chapter 7IMC2000. 4. OSA and exhaust from the bathrooms does not comply with Sec 502.6.3.6IMC2000. |
| 09/13/2001 | INGA DAVIDSON | WATER | REVIEW | Approved | |
| 09/24/2001 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/27/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/04/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ATTACHED TO APPLICATION. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/08/2001 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |