Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM04240
Parcel: 12604012B

Address:
4414 E 2ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM04240
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2001 DAVID RIVERA ZONING REVIEW Approved
10/25/2001 MIKE BERGHUIS FLOODPLAIN REVIEW Approved
10/29/2001 JIM TUCKER FIRE REVIEW Approved
11/16/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ATTACHEDTO APPLICATION
11/19/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumb. See application.
11/19/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mech. See application.
11/20/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Indicate circuit and panel that the receptacles,lights,and exit lighting is fed from.2.Provide panel schedules including loads and drive them back to the service justifying the service,feeders,panel,and circuits are adequate for any increase in load.
11/26/2001 CAGUILAR WWM REVIEW Passed
11/26/2001 TOM CLARK WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2002 DELMA ROBEY OUT TO CUSTOMER Completed