| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/30/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q There also needs to be fire blocking at the ceiling line in the fire partition / plumbing wall detail [2000 IBC Sec. 716.2.2]. Also, the pipes which penetrate through the floor / ceiling assembly must be fire stopped at both the floor and ceiling fire blocking [2000 IBC Sec. 711.4.1]. STRUCTURAL: q There are no structural comments to be addressed. MECHANICAL: q There are no mechanical comments to be addressed. PLUMBING: q There are no plumbing comments to be addressed. ELECTRICAL: q There are no electrical comments to be addressed. -End of Review- |