Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-REVISION/OTHER
Permit Number - T01CM04189
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q The door schedules need to note that all doors within the corridors need to be 20 minute labeled doors. STRUCTURAL: q There are no structural comments to be addressed. MECHANICAL: q The ends of the "breezeways" have been enclosed with walls and doors forming corridors. Provide outside air for these corridors at 0.05 c.f.m. per s.f. [2000 IMC Table 403.3]. PLUMBING: q There are no plumbing comments to be addressed. ELECTRICAL: q Doors have been added to the "breezeways" which have the effect of creating corridors (although these new doors are not shown on the electrical backgrounds). The number of exit signs and their locations needs to be revisited. Many of the signs cannot be viewed within these corridors because of the new doors. Provide additional exit signs. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/09/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |