Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q The door schedules need to note that all doors within the corridors need to be 20 minute labeled doors.

STRUCTURAL:

q There are no structural comments to be addressed.

MECHANICAL:

q The ends of the "breezeways" have been enclosed with walls and doors forming corridors. Provide outside air for these corridors at 0.05 c.f.m. per s.f. [2000 IMC Table 403.3].

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q Doors have been added to the "breezeways" which have the effect of creating corridors (although these new doors are not shown on the electrical backgrounds). The number of exit signs and their locations needs to be revisited. Many of the signs cannot be viewed within these corridors because of the new doors. Provide additional exit signs.