Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM03906
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/09/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 08/09/2001 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 08/10/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/23/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/02/2001 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/05/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. show vents on existing Lav's and WC's. 2. Provide a vent for the P.S. and the grease trap, show on the plan. 3. Provide the manufactures name and listing for all new plumbing fixtures on the plan. |
| 09/05/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Show on the plan how the mechanical design complies with chapter 4 IMC 2000. 2. Provide the manufactures name and lising for the type-I hood. |
| 09/07/2001 | CAGUILAR | WATER | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/11/2001 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 09/07/2001 | CINDY AGUILAR | REJECT SHELF | Completed |