Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T01CM03849
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/01/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E-3 1) Circuit callout LD-20,22 serving Cu-3 should be LDA-20,22. 2) Add the designation SmWP for all fractional horsepower motors. Include a note to read "Provide overload protection not to exceed 1.25 X FLA for both the blower and pump motors" Typical for all evaporative coolers. 3) Remove the #8 designation from the fourplex receptacle served by circuit LD-25. 4) Provide a #10 copper conductor for circuit LDA-9,11. 5) Revise the load calculation. Provide an assessment of the existing HD load (480 volt), existing LD load (208 volt), new LD and LDA loads (208 volt), and the total new HD (480 volt) and LD (208 volt) loads. E-4 1) Circuit LD-3 should be a 15 amp circuit breaker. 2) Clarify exactly how your "isolated grounding system" is intended to be installed. See 99NEC 250-126(d), 250-134(b), and 250-2(d). |
| 11/06/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/09/2001 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |