Review Details: COMMERCIAL TI

Permit Number - T01CM03849
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2001 DAVID RIVERA ZONING REVIEW Approved
08/06/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
08/08/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing Provide a civil site plan with the sewer lines. 2. Provide the correct code in the gas piping notes. ie; 1994 UPC Az. Code.
08/08/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Architectural details do not reflect the M.E.C. calculations. 2. Provide the manufactues name, listing, etc; Per Sec 301.6 IMC 2000 for the paint booth equipment on the plan. 3. Water heater installation shall comply with Sec 701.5 IMC 2000. 4. Show on the plan how the mechanical design complies with Chapter 4 IMC2000.
08/14/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
08/14/2001 MARK TITUS WATER REVIEW Approved
08/15/2001 JIM EGAN FIRE REVIEW Approved
08/28/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
08/29/2001 GERRY KOZIOL WWM REVIEW Approved