Permit Number: T01CM03782
Parcel: 132166260

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM03782
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Denied
08/10/2001 PATRICIA GEHLEN ZONING REVIEW Approved
08/15/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1. bond grounding electrode conductor to neutral at 100 amp service and bond to cabinet . 2. ground rod going to irrigation controller needs to be connected to service grounding electrodes or grounding electrode conductor . 3. provide cut sheets for fixture " B " (this must be in compliance with the outdoor lighting ordinance).

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2001 SUE REEVES OUT TO CUSTOMER Completed