| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 07/30/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 08/06/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) Provide a complete electrical design on full size plan sheets. Provide 2 complete bound sets for review. Include a scaled floor plan depicting the location and names of all panels and electrical equipment. Provide a complete one line service diagram, drive all the loads through each intervening piece of equipment and back to the main service. Demonstrate capacity for the new loads. Balance all panels within 10%. Provide panel schedules with all loads. Provide an electrical floor plan with every new item circuited by number and panel name. Provide a fault current analysis and bracing values for the 70 amp circuit breaker and new panel. |
| 08/07/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/07/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/07/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 08/07/2001 | TOM CLARK | WATER | REVIEW | Passed | |
| 08/27/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/28/2001 | GERRY KOZIOL | WWM | REVIEW | Passed |