Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM03722
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/30/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
07/30/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
08/06/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) Provide a complete electrical design on full size plan sheets. Provide 2 complete bound sets for review. Include a scaled floor plan depicting the location and names of all panels and electrical equipment. Provide a complete one line service diagram, drive all the loads through each intervening piece of equipment and back to the main service. Demonstrate capacity for the new loads. Balance all panels within 10%. Provide panel schedules with all loads. Provide an electrical floor plan with every new item circuited by number and panel name. Provide a fault current analysis and bracing values for the 70 amp circuit breaker and new panel. |
08/07/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Passed | |
08/07/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
08/07/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
08/07/2001 | TOM CLARK | WATER | REVIEW | Passed | |
08/27/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/28/2001 | GERRY KOZIOL | WWM | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/29/2001 | SUE REEVES | OUT TO CUSTOMER | Completed |
08/29/2001 | SUE REEVES | APPROVAL SHELF | Completed |