Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM03721
Parcel: 11301146Z

Address:
1767 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM03721
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) Provide a complete electrical design on full size plan sheets. Provide 2 complete bound sets for review. Include a scaled floor plan depicting the location and names of all panels and electrical equipment. Provide a complete one line service diagram, drive all the loads through each intervening piece of equipment and back to the main service. Demonstrate capacity for the new loads. Balance all panels within 10%. Provide panel schedules with all loads. Provide an electrical floor plan with every new item circuited by number and panel name. Provide a fault current analysis and bracing values for the 70 amp circuit breaker and new panel.
08/07/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
08/07/2001 JIM EGAN FIRE REVIEW Approved
08/07/2001 TOM CLARK WATER REVIEW Passed
08/07/2001 DAN CASTRO ZONING REVIEW Approved
08/27/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
08/28/2001 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2001 SUE REEVES OUT TO CUSTOMER Completed