Permit Number: T01CM03659
Parcel: 108213260

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM03659
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2001 DAVID RIVERA ZONING REVIEW Approved
07/26/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
08/07/2001 JIM EGAN FIRE REVIEW Approved
08/09/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Sheet E-2.2 panel MCB "A" & "B" phases need to be recalulated (may be in error).
08/13/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied 1. Comply with Sec 511.2 UPC 1994 Az. Code on the water heater above the ceiling.
08/13/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Show on the plans how the mechanical design complies with Chapter 4 IMC 2000. 2. Show on the plan how access is made to the equipment on the roof.
08/14/2001 MARK TITUS WATER REVIEW Approved
08/15/2001 GERRY KOZIOL WWM REVIEW Approved
09/21/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2001 SUE REEVES OUT TO CUSTOMER Completed