Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM03659
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/26/2001 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 07/26/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 08/07/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/09/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Sheet E-2.2 panel MCB "A" & "B" phases need to be recalulated (may be in error). |
| 08/13/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comply with Sec 511.2 UPC 1994 Az. Code on the water heater above the ceiling. |
| 08/13/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Show on the plans how the mechanical design complies with Chapter 4 IMC 2000. 2. Show on the plan how access is made to the equipment on the roof. |
| 08/14/2001 | MARK TITUS | WATER | REVIEW | Approved | |
| 08/15/2001 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/21/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/07/2001 | SUE REEVES | OUT TO CUSTOMER | Completed |