Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM03626
Parcel: 11307012A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM03626
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
07/27/2001 JIM EGAN FIRE REVIEW Approv-Cond RESIDENTIAL FIRE SPRINKLERS (NFPA 13R) PROVIDED IN-LIEU OF FIRE APPARATUS ACCESS.
08/01/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing See red lines on the bluelines.
08/01/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical See red lines on the bluelines .
08/02/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E-1
1) Provide a disconnect and grounding electrode system for the house lights and the fire alarm circuit to each apartment building. I would recommend the disconnect be lockable in the closed (on) position to circumvent possible vandalism. Provide appropriate signage to properly identify the purpose of the disconnect. 99NEC 225-31,32 and 250-32
2) Keynote #21 should read #12G not 126 as shown.
E-2 Apartments
1) The peninsular counter receptacles must be mounted in a tombstone receptacle on top of the counter. 99NEC 210-52(c)(5)
2) Add an appliance receptacle on the wall at the beginning of the peninsular counter. 99NEC 210-52(c)
3) See NEC 410-8 regarding the closet lights and provide a compliant design.
4) Provide a 4 conductor circuit for the range and dryer. 99NEC 250-142(b)
5) The circuit number on the plan for the A/C should be A-24,26.
6) The fans must come equipped with a light kit. Please note on plan. 99NEC 210-70(a)(1).
7) Provide complete description of exterior fixtures for both the Apartment and the laundry. Include the source type and wattage.
E-2 Laundry
1) Provide a GFCI receptacle in the bathroom. 99NEC 210-8
2) Place keynotes 5 and 7 and the electrical floor plan.
E-3
1) The A/C load in the unit load calculation appears low; the actual value is 4370VA. As a result of the increase the unit load is approximately 92 amps.
2) Provide the grounding electrode conductor sizes for the services. In addition provide a grounding detail depicting at least the minimum requirements required by 99NEC 250-24 and 250 part C.
3) The 2-unit apartment load analysis is incorrect due to comment E-3 #1 above. The Adjusted 3-unit load using the optional calculation found in 99NEC 220-23 is approximately 186 amps. Using the Standard Calculation found in the 99NEC Part B is only 143 amps.
4) The 3-unit load is approximately 186 amps and the 4-unit load is approximately 248 amps.
5)The utility company will provide both the secondary conductor service laterals and the fault current values at the point of attachment to the building service. Please provide this information on the plan and include it with the second submission.
E-4
1) Specification B under the "Wiring Devices" section requires all receptacles within 6' of a sink to be GFCI protected. The 99NEC 210-8 requires all receptacles serving above countertop kitchen receptacles to be GFCI.
General Comments
1) Provide a symbol list defining all electrical symbols utilized on this project.
2) Please return the blue line set I have already reviewed along with your next submission. It is easily recognizable as it is highlighted in yellow marker.
08/10/2001 MARK TITUS WATER REVIEW Approved
08/14/2001 MICHAEL ST. PAUL ZONING REVIEW Denied
08/15/2001 GERRY KOZIOL WWM REVIEW Denied
09/04/2001 GP BUILDING-COMMERCIAL REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2001 JKOZUCH OUT TO CUSTOMER Completed