Permit Number: T01CM03599
Parcel: 124160190

Address:
1250 S EUCLID AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM03599
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2001 JIM EGAN FIRE REVIEW Approved
07/24/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Denied floodplain use permit required -18th st. Wash
09/24/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied Pg. 13
1) Provide a disconnect for the hot water tank. 99NEC 422-31(b)
Pg. 14
1) Provide fault current analysis and panel withstand rating. 99NEC 110-9
2) Provide Model Energy Lighting Budget Calculations. (Note: The exterior fixtures must be rated a minimum of 45-lumens/watt efficacy. The incandescent fixtures specified are rated approximately 14 to 18 lumens/watt.)
3) Update all references to grounding consistent with the 1999 NEC.
09/26/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Comply with Sec410.7UPC1994 Az. Code. 2. T&P shall discharge to the exterior of the building per Sec608.5UPC1994 Az. Code. Reseal plans with up to date seal.
09/26/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Model energy code calculations missing form plan set. 2. Provide access to the equipment on the roof and show on the plan. 3. Show the condensate lines on the plan,size and discharge location. Reseal plans with up to date seal date.
10/03/2001 INGA DAVIDSON WATER REVIEW Approv-Cond
10/03/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
10/04/2001 DAVID RIVERA ZONING REVIEW Approved
10/05/2001 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/19/2001 CINDY AGUILAR OUT TO CUSTOMER Completed