Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T01CM03599
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/24/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Denied | floodplain use permit required -18th st. Wash |
| 09/24/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Pg. 13 1) Provide a disconnect for the hot water tank. 99NEC 422-31(b) Pg. 14 1) Provide fault current analysis and panel withstand rating. 99NEC 110-9 2) Provide Model Energy Lighting Budget Calculations. (Note: The exterior fixtures must be rated a minimum of 45-lumens/watt efficacy. The incandescent fixtures specified are rated approximately 14 to 18 lumens/watt.) 3) Update all references to grounding consistent with the 1999 NEC. |
| 09/26/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Comply with Sec410.7UPC1994 Az. Code. 2. T&P shall discharge to the exterior of the building per Sec608.5UPC1994 Az. Code. Reseal plans with up to date seal. |
| 09/26/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Model energy code calculations missing form plan set. 2. Provide access to the equipment on the roof and show on the plan. 3. Show the condensate lines on the plan,size and discharge location. Reseal plans with up to date seal date. |
| 10/03/2001 | INGA DAVIDSON | WATER | REVIEW | Approv-Cond | |
| 10/03/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 10/04/2001 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 10/05/2001 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/19/2001 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |