08/29/2001 REYES ARVAYO BUILDING-RESIDENTIAL REVIEW Approved 2000 IRC RESIDENTIAL CHECKLIST

Date: 08-14-01
Re: Project No.T01CM03466 2nd reveiw

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed.

SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical, Model Energy and Electrical codes. All code references are to the 2000 IRC. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

1. Please submit to sets of drawings - some of the corrections where not done- like detail 14/on sheet 10

STRUCTURAL PLANS:

1. Completely detail all connections and cross-reference to the foundation and framing plans:
- Beam to post beam to ext. walls
- Post to slab

ELEVATIONS:

1. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply.

2. Note and dimension that the fireplace chimney must terminate a minimum of 2' above any point of a roof within 10' measured horizontally and not less than 3' above the point where the chimney passes through the roof, per R1001.6.

PLUMBING PLANS:

1. Water Lines: Provide total fixture demand and maximum developed length per P2903, Tables P2903.6 and P2903.7. Redo calc's 1-1/4" to small

2. Waste line for w/c 3" min.

REVIEWED BY REYES ARVAYO 791-5550 EXT. 113