Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2001 JAMES TATE FLOODPLAIN REVIEW Approved
08/06/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Civil site plan indicates a 3" building sewer, plumbing plans indicate a 4" being reduced to 3", this does not comply with Sec 311.5 UPC 1994 Az. Code. Civil site plan also indicates that a backwater valve will be required on the sewer, indicate where on the plan and provide a detail of the access required on the plan. 2. T&P Shall discharge to the exterior of the building. NOTE: The drinking fountain detail on L5 shall be approved by Pima County Dept. of Environmental Quality--- Eric Shepp 740-3959.
08/07/2001 DAN CASTRO ZONING REVIEW Approved
08/08/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E-1
1) The fixture schedule indicates a 100-watt HPS fixture for the basketball ball courts however the submittal indicates a 1000-watt HPS.
2) The entire pole and pole foundation detail does not match the design depicted on page S1, the soils report, or the structural calculations.
E-3
1) It appears the circuitry in the comfort station should be circuited to panel A1 not P1 as shown.
E-4
1) The loads for the basketball lights in the panel appear to be incorrect. Based on a 1000-watt fixture the VA load is approximately 1150 VA per fixture.
2) Provide a fault current analysis and equipment withstand ratings. 99NEC 110-3, 110-9, 110-10.
3) Provide a minimum #4 copper grounding electrode conductor for panel A. 99NEC 250-66
4) Remove the #6 ground in the service lateral. Replace with a minimum #4 cu neutral conductor. 99NEC 250-24(b)
5) Connect the grounding electrode conductor to the neutral and main bonding jumper in panel A. 99NEC 250-28, 250-30(a)(2)
6) Locate the basketball lighting controller contactors on the plan.
7) Provide a grounding electrode system at panel A1. 99NEC 250-32, 250-66
08/13/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
08/15/2001 TOM CLARK WATER REVIEW Approved
08/15/2001 PHIL SEADER BUILDING-COMMERCIAL RECEIVED Completed
09/05/2001 GERRY KOZIOL WWM REVIEW Approved