Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T01CM03173
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2002 | JIM EGAN | FIRE | REVIEW | Denied | MODIFIED COMPRESSOR COVER AND COVERED PORCHES LOCATED TOO CLOSE TO SOUTH PROPERTY LINE. INDICATE FIRE RATINGS OF EXTERIOR WALLS/PROTECTION OF OPENINGS. |
| 01/24/2002 | JOE LINVILLE | NPPO | REVIEW | Approved | Class 1 exception per 1998 aerial. |
| 01/24/2002 | JOE LINVILLE | LANDSCAPE | REVIEW | Denied | Provide screening for the loading area. LUC Sec. 3.4.4.3, Sec 3.4.3.5., Table 3.7.2-I. This applies to loading zones located within 100' of the adjacent HR-3 zoned parcels. Screening is required for the refuse storage area. A 6' wall is required to screen the dumpster pad from the adjacent HR-3 zoned parcel. LUC Table 3.7.2-I A minimum 6'screen is required to screen the refuse storage area from adjacent commercial uses within 100'. |
| 01/30/2002 | PHIL SEADER | HANDICAP-SITE | REVIEW | Approved | |
| 10/08/2001 | DAVID RIVERA | ZONING | REVIEW | Denied | |
| 10/11/2001 | BLANCA ESPINO | SANITATION | REVIEW | Denied | by D. Williams |
| 10/11/2001 | BLANCA ESPINO | ENGINEERING | REVIEW | Denied | by D. Williams |
| 10/11/2001 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2002 | MVALDEZ1 | OUT TO CUSTOMER | Completed |