Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM03125
Parcel: 115211520

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01CM03125
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2001 PATRICIA GEHLEN ZONING REVIEW Denied
09/05/2001 BOB SUBA MECHANICAL-COMMERCIAL REVIEW Denied 1.Indicate the outside air requirements and how this will be accomplished. 2.Where more than one a.c. unit is using the same condensate drain the pipe size must be increased. (note; the pipe cannot be larger than 1" when terminated at the lav. tail piece).3.The model energy calculations need to be sealed by the engineer of record.
09/12/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied SECOND REVIEW
THE ORIGINAL COMMENTS HAVE NOT BEEN ADDRESSED.
E1
1) Provide fixture cuts for all exterior fixtures. The fixture cuts must include catalog numbers that correspond with the lighting schedule. See Light Ordinance 8210 for cut off requirements.
2) The lamp types in the fixture schedule for D and FEM appear to be incorrect.
3) Circuit A-13 requires a load in the panel.
4) Switching must be provided which will provide a uniform 50% reduction of the lighting load in every room except the bathrooms. See 1998 IECC section 705.
E2
1) The bath receptacles must be GFCI protected. 99NEC 210-8
2) Circuit B-14,16,18 serving the single A/C unit should circuit to B-2,4,6.
3) The equipment ground in the tap from the #2 feeders to each A/C must be a minimum of a #8 copper. 99NEC 250-122.
E3
1) The feeder conduit serving panel HP is too small. 99NEC Appendix C.
2) Provide the lateral conductor size, quantity, and material type. NOTE: Do not install an equipment grounding conductor in the lateral. 99NEC 250-30(a)(1) ex1, 250-32(b)1, 310-4, 347-4 ex2.
3) Panel HP should be specified NEMA 3R.
4) It appears note 7 under "Series Rated Information" should reference 99NEC 240-86(a).
E4
1) The City of Tucson has adopted the 99NEC. Please revise all code references to reflect this.
GENERAL COMMENTS
1) Please return the prints I have already reviewed for comparison purposes. This will assist in an expedited second review.
09/14/2001 GERRY KOZIOL WWM REVIEW Denied
09/19/2001 DROBEY BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2001 DELMA ROBEY OUT TO CUSTOMER Completed