Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM03117
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/22/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
06/22/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Passed | |
06/22/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1) PROVIDE COMPLETED CODE REVIEW CHECKLIST. . . ....... S2) CLARIFY ACCESSIBILITY- WHERE IS 20% SPENT ON ACCESSIBILITY- SHOW ON DRAWINGS PER IBC CHAPTERS 11 &34.. . .. ......................................................................................... S3) SHOW ADJACENT TENANT OCCUPANCIES ON DRAWINGS, AND OCCUPANCY SEPARATION REQUIREMENTS.. ........................................................................... S4) PROVIDE NAME AND MODEL NUMBER OF CEILING GRID SUSPENSION MANUFACTURER OR PROVIDE COMPLETE DETAILS OF CEILING GRID SUPPORT SYSTEM. |
06/22/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
06/22/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
06/22/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/22/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/22/2001 | MARK TITUS | WATER | REVIEW | Approved | |
08/01/2001 | TGRIFFUS | WWM | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/01/2001 | TAMI ACHONG | OUT TO CUSTOMER | Completed |