Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T01CM03084
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/28/2001 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
07/20/2001 | DAVE WILLETT | BUILDING-RESIDENTIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/17/2001 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |