Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM02786
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1) CLARIFY OCCUPANCIES AND OCCUPANCY SEPARATIONS ON DRAWINGS: ................................................ ............1. HOURLY FIRE-RATING W/ CONSTRUCTION DETAILS COMPLYING W/LISTING. . . ............................................ ...........2. PROVIDE LISTING / OTHER JUSTIFICATION FOR FIRE ASSEMBLIES ON DRAWINGS. . . . ........................................ ...........3. SHOW OCCUPANT LOADS ON FLOOR PLAN . . ........... ...........4. CLARIFY EXITING FOR SHOWROOM . .......................... S2) SUBMITTAL REQUIRED FOR RE-REVIEW DUE TO SIZE AND COMPLEXITY. . ........................................................................ S3) PROVIDE MINIMUM PLUMBING FIXTURE CALCULATION PER IBC CHAPTER 29. . .................................................................. S4) SHOW ON DRAWINGS ACCESSIBLE PARKING AND COMPLIANCE WITH IBC CHAPTER 11 AND 34. . ......................... S5) FULLY DIMENSION ACCESSIBLE TOILET ROOMS PER IBC CHAPTER 11 AND ICC/ANSI A117.1-1998 ed.. ..................... S6) DETAIL CONNECTIONS OF WALLS TO ADJACENT CONSTRUCTION , INCLUDING STRUCTURE ABOVE AND BELOW WITH FASTENERS (TYPE, SIZE, SPACING/NUMBER). |
| 06/06/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | |
| 06/06/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 06/06/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | |
| 06/14/2001 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 06/15/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/18/2001 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/19/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) Underground service is required. COT Administrative Ordinance Section 108. 2) Building may have one service only. 99NEC 230-2 3) Provide a complete one-line service diagram. Include both the new and existing loads. Provide total code load. See C.O.T. minimum drawing requirements, 99NEC 220. 4) Provide a #10 copper minimum for water heater. Provide a disconnect within sight of the water heater. See 99NEC 310-16 and 422-31(b). 5) One water heater lacks circuitry and a load in panel. See 99NEC 220. 6) Provide GFCI, WP, receptacles within 25' of all roof top HVAC equipment. See 99NEC 210-63, 210-8. 7) Provide conductor, disconnect, and conduit sizes for the new A/C. See 99NEC 440, 310-16. 8) Much of the lighting is overloaded and the individual light fixture loads are incorrect. See 99NEC 220-4(b), 210-19, 384-16(d). 9) Provide proper overload and short circuit protection for the evaporative cooler and pump motors. COT Electrical Code Amendment 99NEC 430-32(e). NOTE: THIS IS A PARTIAL REVIEW ONLY. A FULL REVIEW WILL OCCUR SUBSEQUENT TO NEXT SUBMISSION OF THIS PROJECT. DUE TO THE COMPLEXITY OF THIS PLAN AND IN ACCORDANCE WITH THE STATE BOARD OF TECHNICAL REGISTRATION RULES, AN ELECTRICAL ENGINEER REGISTERED IN THE STATE OF ARIZONA WILL BE REQUIRED TO DESIGN AND SEAL THIS PROJECT. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/22/2001 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |